Agency Approvals
|
IEEE
|
Brand
|
3M™
|
Breakout Boot
|
No
|
Colour Family
|
Grey
|
Conductor Size by Voltage
|
(15 kV, AEIC) 500–750 kcmil, (20 kV, IEC) 240–300 mm², (25 kV, AEIC) 300–500 kcmil, (3.3 kV, JIS) 300–325 mm², (30 kV, IEC) 95–240 mm², (35 kV, AEIC) 4/0 AWG–500 kcmil, (5.0 kV, AEIC) 800–1000 kcmil, (6.6 kV, IEC) 300–325 mm², (8.0 kV, AEIC) 750–1000 kcmil
|
Dielectric Strength (V/mil)
|
428 V/mil
|
Elongation
|
910 %
|
Inner Diameter After Shrink (Imperial)
|
1.3 in
|
Inner Diameter After Shrink (Metric)
|
32.5 mm
|
Inner Diameter Before Shrink (Imperial)
|
1.62 in
|
Inner Diameter Before Shrink (Metric)
|
41.1 mm
|
Insulation Rejacketing
|
Yes
|
Manufacturing Origin
|
USA
|
Metallic Shield Diameter Range
|
1.28 - 1.62 in
|
Operating Temperature (Celsius)
|
105
|
Operating Temperature (Fahrenheit)
|
194
|
Overall Length (Imperial)
|
10 ft
|
Overall Length (Metric)
|
3048 mm
|
Product Colour
|
Dark Grey
|
Product Type
|
Splice Jacketing and Rejacketing Kits
|
Temperature Rating
|
356°F (180°C) Class H
|
Tensile Strength (Imperial)
|
1058 Pound-Force Per Square Inch
|
Units per Case
|
1
|
Voltage Range
|
3.3 - 35 kV
|
3M™ Rejacketing Sleeves RJS Series are designed so that 3M™ Cold Shrink QT-III and Q-TIII Silicone Rubber Terminations can be used on 3/C (three conductor) medium voltage shielded power cables of tape shield, wire shield, armoured and non-armoured configurations. Rejacketing sleeves are designed to protect the phase legs (core) of 3/C shielded power cable from exposure to moisture, corrosion, ozone, ultra-violet radiation, physical contact and other hazards that are associated with termination operating environments. The 3M™ Rejacketing Sleeve RJS-5/10 is to be used in conjunction with 3M™ Cold Shrink Breakout Boots and Silicone Rubber Terminations. 3M™ Rejacketing Sleeve RJS-5/10 has a metallic shield diameter range of 1.28-1.62 inch (32.5-41.1 mm), a voltage range of 3.3-35.0 kV, and one 10-foot (3 m) coil per case.
3M™ Rejacketing Sleeves RJS Series are designed so that 3M™ Cold Shrink QT-III & Q-TIII Silicone Rubber Terminations can be used on 3/C (three conductor) medium voltage shielded power cables of tape shield, wire shield, armoured and non-armoured configurations. Rejacketing sleeves are designed to protect the phase legs (core) of 3/C shielded power cable from exposure to moisture, corrosion, ozone, ultra-violet radiation, physical contact and other hazards that are associated with termination operating environments. 3M™ Rejacketing Sleeve RJS-5/10 are designed to be used in conjunction with 3M™ Cold Shrink Breakout Boots and Silicone Rubber Terminations.
Our goal is to respond to your request within 1-2 business days. Some questions, however, may need further investigation so that we can provide you with an appropriate response.